P80-3000V2 3000VA/2700W Pure Sine Line-Interactive UPS, 2U Rack/Tower, 120V
P80-3000V2 is a 3000VA/2700W, 120V pure-sine line-interactive UPS in a 2U rack/tower chassis, from the Xtreme Power Conversion P80 series.
Specifications
- Model: P80-3000V2 (Xtreme Power Conversion P80 series)
- Capacity: 3000VA / 2700W
- Topology: line-interactive with AVR; pure sine wave output; 2-6 ms typical transfer
- Efficiency: up to 99% in ECO mode, 95% in buck/boost
- Input: 120V, 50/60 Hz; 6 ft L5-30P cord
- Outlets: (6) NEMA 5-15/20R plus (1) L5-30R; programmable receptacle group
- Battery: sealed, maintenance-free lead acid, (6) 12V 9Ah; about 4 hours to 90% recharge
- External batteries: up to two P90-BP72 packs
- Form factor: 2U rack or tower, 17.2 x 23.6 x 3.5 in; rack brackets and tower pedestals included
- Communications: RS-232, USB, EPO, slot for optional Web/SNMP, relay or Modbus card
- Published runtime: about 12 minutes at 50% load and 4 at full load; about 20 minutes at full load with one P90-BP72
Application notes
The P80-3000V2 suits IDF/MDF closets, AV and security racks, telecom and structured-cabling rooms where power is mostly stable and full-time double conversion is not needed. Pure sine output keeps active-PFC power supplies happy, and the programmable outlet group can shed low-priority loads to stretch runtime for core network gear. Add P90-BP72 packs when you need longer runtime.
Manufacturer warranty: 3 years electronics, 3 years battery (USA and Canada), as published by Xtreme Power Conversion.
Source: Xtreme Power Conversion published datasheets and product pages. Runtimes are manufacturer estimates and vary with battery age, temperature and load.
Helpful guides: How to Size a UPS · When to Replace a UPS Battery · Common UPS Failure Points and Preventive Maintenance · UPS and battery service